ABB Relion 670 Series Applications Manual page 464

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 18
Station communication
ANSI13000298 V1 EN-US
Figure 215: Normal operation
Case 2:
Failure of the MU (sample lost) blocks the sending of binary signals through LDCM. The received
binary signals are not blocked and processd normally.
→DTT from the remote end is still processed.
ANSI13000299 V1 EN-US
Figure 216: MU failed, mixed system
Case 3:
Failure of one MU (sample lost) blocks the sending and receiving of binary signals through LDCM.
→DTT from the remote end is not working.
458
ANSI13000298-1-en.vsd
ANSI13000299-1-en.vsd
1MRK 511 358-UUS A
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rec670

Table of Contents