Loss Of Excitation Protection For A Generator - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
This functionality can be achieved by using one CVGAPC function. The following shall be done in
order to insure proper operation of the function:
1.
Connect three-phase generator currents and voltages to one CVGAPC instance (for example,
GF05)
2.
Set
3.
Set
be used for restraining. Alternatively, positive sequence voltage can be used for restraining by
selecting
4.
Set base current value to the rated generator current primary amperes
5.
Set base voltage value to the rated generator phase-to-phase voltage in kV
6.
Enable one overcurrent step (for example, OC1)
7.
Select
8.
If required set minimum operating time for this curve by using parameter
value 0.05s)
9.
Set
10. Set
11. Set
12. Set
13. Set
14. Set
Proper operation of the CVGAPC function made in this way can easily be verified by secondary
injection. All other settings can be left at the default values. Furthermore the other built-in
protection elements can be used for other protection and alarming purposes.
10.1.3.6

Loss of excitation protection for a generator

Example will be given how by using positive sequence directional overcurrent protection element
within a CVGAPC function, loss of excitation protection for a generator can be achieved. Let us
assume that from rated generator data the following values are calculated:
Maximum generator capability to contentiously absorb reactive power at zero active loading
38% of the generator MVA rating
Generator pull-out angle 84 degrees
This functionality can be achieved by using one CVGAPC function. The following shall be done in
order to insure proper operation of the function:
1.
Connect three-phase generator currents and three-phase generator voltages to one CVGAPC
instance (for example, GF02)
2.
Set parameter
3.
Set parameter
4.
Set base current value to the rated generator current primary amperes
5.
Set base voltage value to the rated generator phase-to-phase voltage in kV
6.
Set parameter
7.
Set parameter
8.
Set parameter
9.
Enable one overcurrent step (for example, OC1)
10. Select parameter
11. Set parameter
12. Set parameter
Application manual
CurrentInput to value MaxPh
VoltageInput to value MinPh-Ph (it is assumed that minimum phase-to-phase voltage shall
PosSeq for this setting parameter)
CurveType_OC1 to value ANSI Very inv
PickupCurr_OC1 to value 185%
VCntrlMode_OC1 to On
VDepMode_OC1 to Slope
VDepFact_OC1 to value 0.25
VHighLimit_OC1 to value 100%
VLowLimit_OC1 to value 25%
CurrentInput to PosSeq
VoltageInput to PosSeq
RCADir to value -84 degree (that is, current lead voltage for this angle)
ROADir to value 90 degree
LowVolt_VM to value 5%
CurveType_OC1 to value IEC Def. Time
PickupCurr_OC1 to value 38%
tDef_OC1 to value 2.0s (typical setting)
Section 10
Multipurpose protection
tMin_OC1 (default
M13088-182 v3
237