Section 13
Control
13.4.1

Configuration guidelines

The following sections describe how the interlocking for a certain switchgear configuration can be
realized in the IED by using standard interlocking modules and their interconnections. They also
describe the configuration settings. The inputs for delivery specific conditions (Qx_EXy) are set to
1=TRUE if they are not used, except in the following cases:
989_EX2 and 989_EX4 in modules BH_LINE_A and BH_LINE_B
152_EX3 in module AB_TRAFO
when they are set to 0=FALSE.
13.4.2

Interlocking for line bay ABC_LINE (3)

13.4.2.1

Application

The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a double busbar
arrangement with a transfer busbar according to figure 124. The function can also be used for a
double busbar arrangement without transfer busbar or a single busbar arrangement with/without
transfer busbar.
189
152
989
ANSI04000478 V1 EN-US
Figure 124: Switchyard layout ABC_LINE (3)
The signals from other bays connected to the module ABC_LINE (3) are described below.
13.4.2.2

Signals from bypass busbar

To derive the signals:
302
WA1 (A)
WA2 (B)
WA7 (C)
289
789
189G
289G
989G
en04000478_ansi.vsd
1MRK 511 358-UUS A
M13529-4 v4
IP14139-1 v2
M13561-3 v8
M13560-4 v5
M13560-6 v5
Application manual