Interlocking For Bus-Coupler Bay Abc_Bc (3); Application - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
789_OP = 1
789_CL = 0
7189G_OP = 1
7189G_CL = 0
BB7_D_OP = 1
BC_17_OP = 1
BC_17_CL = 0
BC_27_OP = 1
BC_27_CL = 0
EXDU_BPB = 1
VP_BB7_D = 1
VP_BC_17 = 1
VP_BC_27 = 1
If there is no second busbar WA2 and therefore no 289 disconnector, then the interlocking for 289
is not used. The state for 289, 2189G, BC_12, BC_27 are set to open by setting the appropriate
module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
289_OP = 1
289_CL = 0
2189G_OP = 1
2189G_CL = 0
BC_12_CL = 0
BC_27_OP = 1
BC_27_CL = 0
VP_BC_12 = 1
13.4.3

Interlocking for bus-coupler bay ABC_BC (3)

13.4.3.1

Application

The interlocking for bus-coupler bay (ABC_BC, 3) function is used for a bus-coupler bay connected
to a double busbar arrangement according to figure 128. The function can also be used for a single
busbar arrangement with transfer busbar or double busbar arrangement without transfer busbar.
Application manual
Section 13
Control
IP14144-1 v2
M13555-3 v8
307