1MRK 511 358-UUS A
S TD S
=
EQUATION1893-ANSI V1 EN-US
Where
S
S
old
S
Calculated
TD
The value of
long.
The calibration factors for current and voltage measurement errors are set % of rated current/
voltage:
IMagComp5, IMagComp30, IMagComp100
VMagComp5, VMagComp30, VMagComp100
IAngComp5, IAngComp30, IAngComp100
The angle compensation is given as difference between current and voltage angle errors.
The values are given for operating points 5, 30 and 100% of rated current/voltage. The values
should be available from instrument transformer test protocols.
7.15
Broken conductor check BRCPTOC (46)
7.15.1
Identification
Function description
Broken conductor check
7.15.2
Application
Conventional protection functions can not detect the broken conductor condition. Broken
conductor check (BRCPTOC, 46) function, consisting of continuous current unsymmetrical check
on the line where the IED connected will give alarm or trip at detecting broken conductors.
Application manual
(
)
TD S
1
⋅
+
−
⋅
Old
Calculated
is a new measured value to be used for the protection function
is the measured value given from the function in previous execution cycle
is the new calculated value in the present execution cycle
is settable parameter
TD = 0.92 is recommended in generator applications as the trip delay is normally quite
IEC 61850
IEC 60617
identification
identification
BRCPTOC
-
Current protection
(Equation 89)
ANSI/IEEE C37.2
device number
46
Section 7
SEMOD171761-1 v3
SEMOD172362-2 v2
SEMOD171858-5 v3
189