Pole Discrepancy Protection Ccpdsc(52Pd); Identification; Application; Setting Guidelines - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
IPickup : Current level for the Stub protection, set in % of IBase . This parameter should be set so
that all faults on the stub can be detected. The setting should thus be based on fault calculations.
t : Time delay of the operation. Normally the function shall be instantaneous.
7.12

Pole discrepancy protection CCPDSC(52PD)

7.12.1

Identification

Function description
Pole discrepancy protection
7.12.2

Application

There is a risk that a circuit breaker will get discrepancy between the poles at circuit breaker
operation: closing or opening. One pole can be open and the other two closed, or two poles can be
open and one closed. Pole discrepancy of a circuit breaker will cause unsymmetrical currents in the
power system. The consequence of this can be:
Negative sequence currents that will give stress on rotating machines
Zero sequence currents that might give unwanted operation of sensitive ground-fault
protections in the power system.
It is therefore important to detect situations with pole discrepancy of circuit breakers. When this
is detected the breaker should be tripped directly.
Pole discordance protection CCPDSC (52PD) will detect situation with deviating positions of the
poles of the protected circuit breaker. The protection has two different options to make this
detection:
By connecting the auxiliary contacts in the circuit breaker so that logic is created, a signal can
be sent to the protection, indicating pole discrepancy. This logic can also be realized within
the protection itself, by using opened and close signals for each circuit breaker pole,
connected to the protection.
Each phase current through the circuit breaker is measured. If the difference between the
phase currents is larger than a
protection will operate.
7.12.3

Setting guidelines

The parameters for the Pole discordance protection CCPDSC (52PD) are set via the local HMI or
PCM600.
Application manual
IEC 61850
IEC 60617
identification
identification
CCPDSC
PD
SYMBOL-S V1 EN-US
CurrUnsymPU this is an indication of pole discrepancy, and the
Current protection
ANSI/IEEE C37.2
device number
52PD
Section 7
IP14516-1 v5
M14888-1 v4
M13270-3 v6
M13274-3 v8
177