Section 15
Logic
Name of input
IN14
IN15
IN16
The sum of the numbers in column "Value when activated" when all INx (where 1≤x≤16) are active
that is=1; is 65535. 65535 is the highest boolean value that can be converted to an integer by the
B16I function block.
15.9
Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC
15.9.1
Identification
Function description
Boolean to integer conversion with
logical node representation, 16 bit
15.9.2
Application
Boolean 16 to integer conversion with logic node representation function BTIGAPC is used to
transform a set of 16 binary (logical) signals into an integer. BTIGAPC can receive an integer from a
station computer – for example, over IEC 61850–8–1. These functions are very useful when you
want to generate logical commands (for selector switches or voltage controllers) by inputting an
integer number. BTIGAPC has a logical node mapping in IEC 61850.
The Boolean 16 to integer conversion function (BTIGAPC) will transfer a combination of up to 16
binary inputs INx where 1≤x≤16 to an integer. Each INx represents a value according to the table
below from 0 to 32768. This follows the general formula: INx = 2
values on the activated INx will be available on the output OUT as a sum of the values of all the
inputs INx that are activated. OUT is an integer. When all INx where 1≤x≤16 are activated that is =
Boolean 1 it corresponds to that integer 65535 is available on the output OUT. BTIGAPC function is
designed for receiving up to 16 booleans input locally. If the BLOCK input is activated, it will freeze
the output at the last value.
Values of each of the different OUTx from function block BTIGAPC for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block BTIGAPC.
408
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
IEC 61850
identification
BTIGAPC
Description
Value when
activated
Input 14
8192
Input 15
16384
Input 16
32768
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
x-1
where 1≤x≤16. The sum of all the
1MRK 511 358-UUS A
Value when
deactivated
0
0
0
SEMOD175753-1 v4
SEMOD175757-2 v5
SEMOD175849-4 v5
Application manual