Section 18
18.1
Communication protocols
Each IED is provided with a communication interface, enabling it to connect to one or many
substation level systems or equipment, either on the Substation Automation (SA) bus or
Substation Monitoring (SM) bus.
Available communication protocols are:
IEC 61850-8-1 communication protocol
IEC 61850-9-2LE communication protocol
LON communication protocol
SPA or IEC 60870-5-103 communication protocol
DNP3.0 communication protocol
Several protocols can be combined in the same IED.
18.2
IEC 61850-8-1 communication protocol
18.2.1
Application IEC 61850-8-1
IEC 61850-8-1 communication protocol allows vertical communication to HSI clients and allows
horizontal communication between two or more intelligent electronic devices (IEDs) from one or
several vendors to exchange information and to use it in the performance of their functions and
for correct co-operation.
GOOSE (Generic Object Oriented Substation Event), which is a part of IEC 61850–8–1 standard,
allows the IEDs to communicate state and control information amongst themselves, using a
publish-subscribe mechanism. That is, upon detecting an event, the IED(s) use a multi-cast
transmission to notify those devices that have registered to receive the data. An IED can, by
publishing a GOOSE message, report its status. It can also request a control action to be directed
at any device in the network.
Figure 209
interface to the substation LAN. The LAN itself is left to the system integrator.
Application manual
Station communication
shows the topology of an IEC 61850–8–1 configuration. IEC 61850–8–1 specifies only the
Section 18
Station communication
M14815-3 v12
IP14616-1 v2
IP14865-1 v2
M13912-3 v4
M13913-3 v4
449