Section 16
Monitoring
16.7.1
Identification
Function description
Logical signal status report
16.7.2
Application
The Logical signal status report (BINSTATREP) function makes it possible for a SPA master to poll
signals from various other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs and can be read
from the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the input signal
remains set for a longer period, the output will remain set until the input signal resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 205: BINSTATREP logical diagram
16.7.3
Setting guidelines
The pulse time
can be set or reset individually, but the pulse time will be the same for all outputs in the entire
BINSTATREP function.
16.8
Fault locator LMBRFLO
16.8.1
Identification
Function description
Fault locator
16.8.2
Application
The main objective of line protection and monitoring IEDs is fast, selective and reliable operation
for faults on a protected line section. Besides this, information on distance to fault is very
440
IEC 61850
identification
BINSTATREP
t
t is the only setting for the Logical signal status report (BINSTATREP). Each output
IEC 61850
identification
LMBRFLO
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
t
IEC09000732-1-en.vsd
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
1MRK 511 358-UUS A
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
GUID-F9D225B1-68F7-4D15-AA89-C9211B450D19 v2
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
IP14592-1 v2
M14892-1 v3
M13752-3 v6
Application manual