Switch Controller (Scswi) - ABB Relion 670 Series Applications Manual

Bay control, version 2.1 ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK 511 358-UUS A
IEC13000016 V2 EN-US
Figure 119: APC - Local remote function block
13.3.1.2

Switch controller (SCSWI)

SCSWI may handle and operate on one three-phase device or three one-phase switching devices.
After the selection of an apparatus and before the execution, the switch controller performs the
following checks and actions:
A request initiates to reserve other bays to prevent simultaneous operation.
Actual position inputs for interlocking information are read and evaluated if the operation is
permitted.
The synchronism check/synchronizing conditions are read and checked, and performs
operation upon positive response.
The blocking conditions are evaluated
The position indications are evaluated according to given command and its requested
direction (open or closed).
The command sequence is supervised regarding the time between:
Select and execute.
Select and until the reservation is granted.
Execute and the final end position of the apparatus.
Execute and valid close conditions from the synchronism check.
Application manual
IEC13000016-2-en.vsd
Section 13
Control
M16596-3 v4
293