Inrush-Current Detection/Blocking

4.1.25
The device detects the presence of high level of 2nd harmonic current. For example, a transformer inrush
current. If the 2nd harmonic current is greater than 15 % of the measured phase current of any of the 3
phases, the device does not issue a fault indication for the set threshold I>, tI>, I
persists for more than the configured CrossBlockTimer value, then the device displays a fault indication. The
device does not block the fault indication if the fault current is above the set threshold I>> for the time tI>>.
If the fault current persists for the respective time setting (tI> for phases, tI
blocking function monitors the inrush current. The inrush current is detected by analyzing the magnitude of
the 2nd harmonic components of the phase vectors.