Bit-Type Data - Siemens SICAM Manual

Feeder condition monitor
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

B.3

Bit-Type Data

Table B-10
Address
Bit Type
1
Activate self-test mode
2
Reset device
3
Reset fault
4
Reserved for future use
5
Digital output 1 (DO1)
6
Digital output 2 (DO2)
7
Clear data available status
8
Clear event database
9
Initiate auto calibration
10
Energy counter reset
11
Password reset
12
Active-group switching
Table B-11
Address
Bit Type
1
Status data/data available
2
Self-test mode activated
3
Overcurrent (I>>), high-set
without direction indication
4
Ground-fault tripping (I
5
Overvoltage warning (V
Warning)
6
Overvoltage alarm (V
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Bit-Type Data – Coil
Bit-Type Data – Discrete Input
>)
N
min
Alarm 1
max
Data
Description
1
Setting to 1 activates the incorporated self-test.
Reboots the device.
1
Setting to 1 deactivates the LED event indicator
and tripped event-related DOs. It also resets the
register for the events and display.
The device sets the bit automatically to 0.
-
This bit indicates the status of the DO1 and used
for indicating fault in the forward direction.
This bit indicates the status of the DO2 and used
for indicating fault in the reverse direction.
1
Deletes the available status of the data.
Enabling this address restarts the self-test mode.
1
Deletes the event database.
Enabling this address clears all the events only if
there is no fault condition.
1
Initiates the autocalibration of the device
1
Resets all the energy counters to zero.
1
Reset the password to the default value (1111),
only if the password protection is enabled in the
device.
1
Toggles the active group between group 1 and
group 2.
Data
Description
1
New data available
0
No new data available
The bit is set to 1 on occurrence of I
overcurrent alarm, overvoltage warning, under-
voltage warning, overvoltage alarm, or under-
voltage alarm. The status data can be cleared if
the user sets the value of the Bit-type data - Coil,
Clear data available status
1
Incorporated self-test mode activated
0
Incorporated test mode not activated
1
Overcurrent indication detected
0
No overcurrent indication detected
1
I
> indication detected
N
0
No I
> indication occurred
N
1
Overvoltage warning detected
0
No overvoltage warning detected
Overvoltage alarm detected
0
No overvoltage alarm detected
Modbus Registers
B.3 Bit-Type Data
>, I >, I>>,
N
107