B.3
Bit-Type Data
Table B-10
Address
Bit Type
1
Activate self-test mode
2
Reset device
3
Reset fault
4
Reserved for future use
5
Digital output 1 (DO1)
6
Digital output 2 (DO2)
7
Clear data available status
8
Clear event database
9
Initiate auto calibration
10
Energy counter reset
11
Password reset
12
Active-group switching
Table B-11
Address
Bit Type
1
Status data/data available
2
Self-test mode activated
3
Overcurrent (I>>), high-set
without direction indication
4
Ground-fault tripping (I
5
Overvoltage warning (V
Warning)
6
Overvoltage alarm (V
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Bit-Type Data – Coil
Bit-Type Data – Discrete Input
>)
N
min
Alarm 1
max
Data
Description
1
Setting to 1 activates the incorporated self-test.
–
Reboots the device.
1
Setting to 1 deactivates the LED event indicator
and tripped event-related DOs. It also resets the
register for the events and display.
The device sets the bit automatically to 0.
–
-
–
This bit indicates the status of the DO1 and used
for indicating fault in the forward direction.
–
This bit indicates the status of the DO2 and used
for indicating fault in the reverse direction.
1
Deletes the available status of the data.
Enabling this address restarts the self-test mode.
1
Deletes the event database.
Enabling this address clears all the events only if
there is no fault condition.
1
Initiates the autocalibration of the device
1
Resets all the energy counters to zero.
1
Reset the password to the default value (1111),
only if the password protection is enabled in the
device.
1
Toggles the active group between group 1 and
group 2.
Data
Description
1
New data available
0
No new data available
The bit is set to 1 on occurrence of I
overcurrent alarm, overvoltage warning, under-
voltage warning, overvoltage alarm, or under-
voltage alarm. The status data can be cleared if
the user sets the value of the Bit-type data - Coil,
Clear data available status
1
Incorporated self-test mode activated
0
Incorporated test mode not activated
1
Overcurrent indication detected
0
No overcurrent indication detected
1
I
> indication detected
N
0
No I
> indication occurred
N
1
Overvoltage warning detected
0
No overvoltage warning detected
Overvoltage alarm detected
0
No overvoltage alarm detected
Modbus Registers
B.3 Bit-Type Data
>, I >, I>>,
N
107