Select one of the following Measured-value output options:
–
Table
The determined results are displayed in a table. In the multi-page tables, you can show the forward
and backward pages with the >> and << buttons. If you want to view a certain page, enter the page
number at the bottom and click show.
–
Diagram
You can view 1-day or 1-week records with a diagram. The user interface requires the SIGRA Plug-in.
For more information on the SIGRA plug-in, contact the Siemens Hotline.
•
Click Display
Transient Detection
2.5.7
2.5.7.1
Transients
The device detects temporary overvoltages as transients if the instantaneous value of the primary rated
voltage exceeds the parameterized reference value at one or several sampling points. Detect and capture tran-
sients as short as 100 μs at 50 Hz (80 μs at 60 Hz).
The following data and values are determined during the evaluation of the transients in the device:
•
Serial number of the event
•
Time when transients start to occur (time stamp with date and time)
•
Affected phase (a, b, c, ab, bc, ca)
•
Transient duration
Parameterized reference value (in %) is up to 240 % of the primary rated voltage.