Modbus Registers
B.2 Implementation of the Modbus Protocol
Address Min/Max Value
1040
0 to 65535
1041
-1000 to 1000
1042
-32768 to 32767 3-phase active power
1043
-32768 to 32767 3-phase reactive power
1044
0 to 65535
1045
-2 147 483 648
to
2 147 483 647
1046
1047
-2 147 483 648
to
2 147 483 647
1048
1049
-2 147 483 648
to
2 147 483 647
1050
1051
-2 147 483 648
to
2 147 483 647
1052
1053
0 to 65535
1054
0 to 65535
102
Parameters
3-phase apparent power
3-phase power factor
3-phase apparent power
Active import energy
Active export energy
Reactive import energy
Reactive export energy
Firmware major and maintenance version
number
Application firmware and build version
number
Unit
Type
1/10 kVA for 230-V
uInt16
sensor
1/100 MVA for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
sInt16
1/10 kW for 230-V
sInt16
sensor
1 kW for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1/10 kVAr for 230-V
sInt16
sensor
1 kVAr for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1/10 kVA for 230-V
uInt16
sensor
1 kVA for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1 kWh for 230-V
uInt32
sensor
1 MWh for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1 kWh for 230-V
uInt32
sensor
1 MWh for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1 kVArh for 230-V
uInt32
sensor
1 MVArh for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1 kVArh for 230-V
uInt32
sensor
1 MVArh for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
uInt16
uInt16
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019