Siemens SICAM Manual page 86

Feeder condition monitor
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Parameterization
A.2 Parameterizing the User Interface
86
TIME SETTING
tV
>
NG
I
dir
NEUTRAL-POINT
TREATMENT
GROUP2
GROUND-FAULT
SETTING
DETECTION I
GROUND-FAULT
DETECTION tI
THRESHOLD
SETTING V
TIME SETTING
tV
>
NG
I
dir
NEUTRAL-POINT
TREATMENT
V<
0 % to 100 %
(Set to "0" to disable the detection function)
SAVE
V>
0 % to 170 %
(Set to "0" to disable the detection function)
SAVE
PULSE
3I0 DELTA
DETEC-
TION
PULSE
TPULSE ON
DETEC-
TION
TPULSE OFF
0.04 s to 60 s
SAVE
0.2 A to 30 A
(Set to "0" to disable the
cos ϕ/sin ϕ method)
SAVE
SOLID or ISOLATED or RESO-
NANT
SAVE
0.4 A to 2000 A
>
(Set to "0" to disable the
N
detection function)
SAVE
0.04 s to 60 s
>
N
SAVE
0 % to 100 %
>
(Set to "0", the ground-fault
NG
detection is based on I
SAVE
0.04 s to 60 s
SAVE
0.2 A to 30 A
(Set to "0" to disable the
cos ϕ/sin ϕ method)
SAVE
SOLID or ISOLATED or RESO-
NANT
SAVE
0 % to 300 %
(Set to "0" to disable the
detection function)
SAVE
0.50 s to 20 s
(Set to "0" to disable the
detection function)
SAVE
0.50 s to 20 s
(Set to "0" to disable the
detection function)
SAVE
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
>)