Hardware Components and Drawings
3.2 Terminal Diagram
Terminal Connections
You can connect the device terminals with a wire of cross-section ranging from 0.75 mm
following options to connect the terminals:
Spring-cage connection
Spring-cage connection is used to connect the upper row of terminals. From terminal 1 to terminal 12.
Screw connection
Screw connection is used to connect the bottom row of terminals. From terminal 13 to terminal 24.
The following tables show the technical details of the different connection methods.
Table 3-2
Connection Elements
Connection method
Conductor size (solid)
Conductor size (stranded)
Stripping length
AWG (max.)
AWG (min.)
Table 3-3
Connection Elements
Connection method
Conductor size (solid)
Conductor size (stranded)
Stripping length
AWG (max.)
AWG (min.)
Torque
Screwdriver size
24
Spring-Cage Connection
Screw Connection
Specifications
Spring cage
4.0 mm
2
2.5 mm
2
8.0 mm
12.0
24.0
Specifications
Screw connection
1.0 mm
2
1.0 mm
2
8.0 mm
16.0
26.0
0.5 Nm
3/32 inch or 2.5 mm
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
2
to 2.5 mm
2
. Use the