Technical Data
5.1 Device Technical Data
Digital Inputs
Number
External operating voltage
Digital Outputs
Number
Type
Maximum switching capacity
Permissible current per contact (continuous)
Permissible current per contact (switching)
Dimensions
Type of fixing
Cut-out (W x H)
Overall depth
Permissible switch panel thickness for installation
Mounting position
Weight
Environment
Operating temperature range
Storage temperature range
Humidity range
Altitude above sea level
Protection Device Class
Device front
Device rear
Power Consumption
DC 24 V/AC 230 V
Peak power during power on
NOTE
i
i
When the auxiliary power supply fails, the device is switched on with an internal battery. In this low-power
mode, the device has limited functionality.
In the low-power mode, you can reset a fault, set parameters, and view events/records. In this mode, meas-
urements, fault detection, and communication functions are not available.
64
1
DC 24 V to 30 V continuous signal
DC 30 V to 60 V periodic
0.5 s ON time and 4.5 s OFF time
2
Dry contact
2000 VA (AC, resistive)
240 W/30 V DC (DC, resistive)
8 A
8 A
Panel flush mounting
92+0.8 mm x 45+0.8 mm
109.5 mm
2 mm to 4 mm
Horizontal
≤ 500 g
-40 °C to +70 °C
-25 °C to +55 °C
0 % to 95 %, non-condensing
Maximum up to 2000 m
IP 40
IP 20
0.8 W
6.0 W