Siemens SICAM Manual page 100

Feeder condition monitor
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Modbus Registers
B.2 Implementation of the Modbus Protocol
Table B-6
Address Min/Max Value
1000
0 to 65535
1001
0 to 65535
1002
0 to 65535
1003
0 to 65535
0 to 9999
1004
0 to 65535
1005
0 to 65535
1006
0 to 65535
1007
0 to 65535
1008
0 to 65535
1009
0 to 65535
1010
0 to 65535
1011
0 to 3599
1012
0 to 3599
100
Input Registers
Parameters
Phase current I
Phase current I
Phase current I
Ground current I
systems
Ground current I
Voltage V
12
Voltage V
23
Voltage V
31
Voltage V
1
Voltage V
2
Voltage V
3
Displacement voltage V
Phase angle I
1
Phase angle I
2
1
2
3
for compensated/isolated
N
for grounded systems
N
NG
Unit
Type
A
uInt16
A
uInt16
A
uInt16
1/100 A
uInt16
A
1/10 V for 230-V
uInt16
sensor
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1/10 V for 230-V
uInt16
sensor
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1/10 V for 230-V
uInt16
sensor
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1/10 V for 230-V
uInt16
sensor
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1/10 V for 230-V
uInt16
sensor
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1/10 V for 230-V
uInt16
sensor
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1/10 V for 230-V
uInt16
sensor
1/100 kV for 3.25/√3
sensor, for 100/√3
sensor, and for 400/√3
sensor
1/10°
uInt16
1/10°
uInt16
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019