Fault-Reset Mechanism - Siemens SICAM Manual

Feeder condition monitor
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Device Functions
4.1 Description
NOTE
i
i
For isolated/compensated systems in case of 2-phase-to-ground and 3-phase-to-ground faults, whenever a
ground fault and phase fault occur at a same time, SICAM FCM indicates phase fault as a priority event on
HMI/Modbus.
For more information about direction determination, refer to
4.1.16 Direction Determination of Phase
Grounded)
, and
For more information about fault-detection parameters, see
Detection menu and

Fault-Reset Mechanism

4.1.3
The fault status of the device can be reset through anyone of the following mechanisms:
Auto reset as per user-defined time setting
Digital input (DC 24 V to DC 60 V)
User interface through keypad (Reset)
RS485/Modbus interface
The following logic diagram shows the fault-reset mechanism.
[lo_sfcm_faultresetmech, 2, en_US]
Figure 4-3
(1)
Binary contact 1, indication on HMI and Modbus, event logs
(2)
Binary contact 2, indication on HMI and Modbus, event logs
(3)
Binary contact 1 and Binary contact 2, indication on HMI and Modbus, event logs
32
Elements,
4.1.18 Directional Ground Fault (in Isolated Electrical Power
Table A-3
for the Fault Parameters > Ground-Fault Detection menu.
Logic Diagram for Fault Indication and Fault Reset Mechanism
4.1.15 Determination of Fault
4.1.17 Directional Ground Fault (Compensated/Resonant-
Systems).
Table A-2
for the Fault Parameters > Phase-Fault
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Direction,