Mechanical Tests
Table 6-4
Tests
Vibration response
test
Vibration withstand
test
Shock response test
Shock withstand test IEC 60068-2-27, Class I
EMI/EMC Tests for Immunity
Table 6-5
Test
Electrostatic
discharge immunity
test
Electromagnetic high
frequency distur-
bance (Radiated
Susceptibility Test)
Electrical fast tran-
sient/burst immunity
test
Surge immunity test
Conducted suscepti-
bility test
Damped oscillatory
wave immunity test
Power frequency
magnetic field
Voltage dips and
interruptions
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
Mechanical Tests
Standards
IEC 60068-2-6, Class I
IEC 60068-2-6, Class I
IEC 60068-2-27, Class I
Immunity Test
Standards
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 3
IEC 61000-4-5, Level 3
IEC 61326-1, Level 3
IEC 61000-4-6, Level 2
IEC 61326-1, Level 2
IEC 61000-4-18, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11,
IEC 61000-4-29,
IEC 61326-1
Test Requirements
Sinusoidal
10 Hz to 150 Hz: ± 0.035 mm amplitude, 0.5 g acceleration,
frequency sweep rate 1 octave/min, 1 cycle in 3 orthogonal
axes
Sinusoidal
10 Hz to 150 Hz: ± 0.075 mm amplitude, 1 g acceleration,
frequency sweep rate 1 octave/min, 20 cycles in 3 orthog-
onal axes
Acceleration 5 g, duration 11 ms, 18 shocks each in both
directions of the 3 orthogonal axes
Acceleration 15 g, duration 11 ms, 18 shocks each in both
directions of the 3 orthogonal axes
Test Requirements
8 kV air discharge and 6 kV contact discharge
80 MHz to 1 GHz (10 V/m, Criteria B) and
1.4 GHz to 2.7 GHz (10 V/m, Criteria B)
± 4 kV on auxiliary power supply, current inputs, voltage
inputs, digital input, and digital outputs
± 2 kV on communication port
± 2 kV DM, ± 4 kV CM on auxiliary power supply and
voltage inputs
± 1 kV DM, ± 2 kV CM on digital input and digital outputs
± 4 kV on current inputs
± 2 kV on communication port
150 kHz to 80 MHz (3 V) on auxiliary power supply, current
inputs, voltage inputs, digital input, digital outputs, and
communication port
2.5 kV (CM), 1.0 kV (DM) applied on current inputs, voltage
inputs, digital input, digital outputs, and communication
port
(1 MHz, 100 kHz)
30 A/m (continuous field) and 300 A/m pulsed (short dura-
tion for 3 s) on the X, Y, Z axis of the product
0 %, 40 %, and 70 % dips on AC/DC power supply
0 % short interruptions for 250/300 cycles (50 Hz/60 Hz)
Type Testing
6.1 Type Testing
67