AC connection
6. Anchor cable with clamp bar.
7. Close and latch power supply terminal protection cover.
8. Tighten cable gland.
5.9
Missing PE/ground connection
Missing PE/ground connection
Danger of electric shock.
Depending on the device version, connect the power supply as follows:
Connecting terminals: Connect the terminals according to the terminal connection
5.10
Step 4a: Connecting the current output HART (channel 1)
Note
HART communication
It is recommended to use shielded cables for HART communication.
Passive channels only
Channel 1 power supply must be separated from that for channels 2 to 4.
Signal return (or common) can be joined.
1. Remove cap and ferrule from cable gland and slide onto cable.
2. Push cable through open gland and cable path.
SITRANS FC430 with HART
Operating Instructions, 03/2012, A5E03361511-01
Power: 100 to 240 V AC +10/-15%, 47 to 63 Hz
WARNING
diagram. First connect the PE/ground conductor.
WARNING
5.9 Missing PE/ground connection
DC connection
Power: 24 to 90 V DC +20/-20%
Connecting
63