Alternately, auto calibration can be done by turning on the Modbus coil Address 9.
²
[dw_sfcmdevautocalib, 1, en_US]
Figure 4-23
Press OK to start the auto calibration.
²
The auto calibration takes about 60 s to complete.
The following dialog appears:
[dw_sfcmdevautocalib_msg, 1, en_US]
Figure 4-24

Energy Measurement

4.1.33
The device provides counters in the Modbus registers to acquire the following data:
Active import energy
Active export energy
Reactive import energy
Reactive export energy
The values are kept when the device is powered off or in sleep mode. The counter starts incrementing from
the last stored value once the device is powered on.
For more information about these counters, refer to
The counter value can be reset by any one of the following methods:
Using the Energy counter reset parameter via HMI
Using the Energy counter reset Modbus register. For more information, refer to

RTC Synchronization

4.1.34
The device provides an internal real-time clock. In order to get an external time synchronization, the device
must be synchronized with the Modbus master with the current system time. The real-time clock must be
synchronized at least once a day for a valid time stamp.
The device needs a time synchronization, when it resumes from the sleep mode to ensure the correct time and
date. Also the time synchronization is required when the device is powered on after 8 hours of sleep mode.
SICAM, Feeder Condition Monitor, Manual
E50417-H8940-C580-A4, Edition 03.2019
VDS Device Auto Calibration
Device Auto Calibration
3-Phase Active Import Energy Counter, Page
Device Functions
4.1 Description
139.
Table
B-10.
55

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents