Siemens SITRANS P300 Quick Start Guide
Also See for SITRANS P300:

Advertisement

Siemens SITRANS P300 Quick Start Guide

warning Please refer to the Instruction Manual prior to installation and startup!

Overview

Overview

Connection box

Connection Box Overview

  1. Screen connection
  2. PROFIBUS-PA
  3. PROFIBUS-PA
  4. Mode key
  5. Increment key
  6. Decrement key

Digital display

Digital Display Overview

  1. Measured
  2. Dimension/Fault code
  3. Root display (Flow)
  4. Mode/Simulation/Protection →
    L Keyboard and Function value
  5. Violation of lower limit
  6. Sign for measured value
  7. Violation of higher limit
  8. Communication display

Operation

Measured value, Unit (M12 and M14), status
Error and fault codes in case of malfunction
M4 Damping1)2)
M7 Zero adjustment3)2)
M10 Key and function disable1)5)2)
M13 Measured value source1)2)
M14 Physical unit1)3)2)
M15 Bus address1)2)
M16 Device operation mode1)2)
M17 Decimal point1)2)
M18 Zero adjustment4)
M19 Balance LO1)3)2)
M20 Balance HI1)3)2)

1) UP or DOWN change value

2) MODE save value

3) UP and DOWN 2s set value

4) Only display of remaining available measuring range

5) UP and DOWN 2s lock off

Fault codes

F_001 Key and function disable
F_003 Change of device mode currently not permitted
F_004 Decimal point unfavourable
F_005 Value is read-only
F_006 Balance span too small
F_007 Measuring range limited
F_008 Local operation disabled

Status bad

B_004 Balance span too small
B_011 Value not calculated
B_012 Electronics defective
B_015 Electronics defective, value constant
B_016 Sensor error
B_017 Lower overrange limit reached
B_018 Upper overrange limit reached
B_031 Out of service

Status unsafe

U_071 Last usable value
U_072 Substitute value
U_075 Substitute value constant
U_079 Initial value
U_080 Maintenance alarm
U_081 Lower measuring range reached
U_082 Upper measuring range reached

Status good

Good
G_132 Parameter changed
G_137 Lower warning limit reached
G_138 Upper warning limit reached
G_141 Lower alarm limit reached
G_142 Upper alarm limit reached
G_164 Maintenance required

Mode 13: measured value source

0 Output
1 Secondary variable (Pressure)
2 Primary variable
3 Sensor temperature
4 Electronics temperature
5 Secondary variable 3
6 Counter output
7 Sensor pressure value

Mode 16: device operation mode

0 Profile 3.0 device (1AI)
1 SITRANS P DS III PA Profile 3.0
128 Profile 3.0 Gerät (1AI, 1TOT)

Mode 19, 20: Balance

  • Select mode 19.
  • Enter the reference pressure (LO) on the transmitter
  • With1) the display switches to the measured pressure value, select the value of the reference pressure.
  • With3) the lower balance point is applied.
  • Select mode 20,
  • Enter the reference pressure (HI) on the transmitter.
  • With1) the display switches to the measured pressure value, select the value of the reference pressure.
  • With3) the upper balance point is applied

FW/HW releases

Can be read from the approval label

FW: aaaa. bb. cc

HW: xx. yy. zz

Connecting the transmitter

Connecting the Transmitter

  1. Supply terminals
  2. A. Shield on cable gland
    B. Guide channel
  3. Auxiliary power UH

Ex-Data

See operation instructions, type plate and certificate of conformity http://www.siemens.com/sitransp

Documents / Resources

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Siemens SITRANS P300 Quick Start Guide