Technical data
9.1
PAC4220 technical data
Device configuration
• 2 slots for up to 2 optional expansion modules
• 2 opto-isolated digital inputs
• 2 opto-isolated digital outputs
• 2 Ethernet interfaces for connecting to the PC or network
Measurement
Only for connection to alternating voltage systems
Measuring method
For voltage measurement
For current measurement
Measured value acquisition
Measuring inputs for voltage
Measuring inputs for voltage
Measurable voltage
Zero point suppression
Measuring category
(acc. to IEC/UL 61010-2-030)
PAC4220
Equipment Manual, L1V30827278B-01
True root mean square measurement (TRMS), zero blind measurement,
gapless, up to the 64th harmonic
True root mean square measurement (TRMS), zero blind measurement,
gapless, up to the 64th harmonic
•
Power
•
Frequency
•
Power factor
•
cos φ
Waveform
Frequency of the relative funda‐
mental
Measured value acquisition mode Automatic line frequency detec‐
Rated voltage
Min. measuring voltage U
Max. measuring voltage U
Voltage L-N
Voltage L-L
Category
Impulse withstand voltage
Zero blind measurement, gapless
Sinusoidal or distorted
50/60 Hz
tion
57.7/100 ... 400/690 V (IEC)
57.7/100 ... 347/600 V (UL)
L-N
480 V (IEC)
L-N
416 V (UL)
10 V
17 V
CAT III
≥ 9.6 kV (1.2/50 µs)
9
101