Siemens SIMATIC S7-300 Getting Started page 71

Automation system, cpu 317tf-3pn/dp: controlling a sinamics s120 with safety functions
Hide thumbs Also See for SIMATIC S7-300:
Table of Contents

Advertisement

Step
Activity
8
In the "Safely limited speed" dialog, enter 500 ms under "Delay time between sel. SLS --> SLS active".
Change the velocity value Vmax for Stage 1 to 1200 mm/min.
Click "Close" to confirm the entries and close the "Safely limited speed" dialog.
9
Click "Copy parameters" in the "Safety integrated" dialog.
10
Click "Activate settings" in the "Safety integrated" dialog.
You are prompted to change the safety password for the drive.
Enter a safety password for the drive.
11
You are prompted to save the safety parameters.
Select "Parameters of the drive device".
12
In S7T Config, select the Project > Disconnect from target system menu command to switch to the offline mode.
13
Switch off the SINAMICS S120 drive system (de-energize) and switch it on again.
14
Once the device has completed its startup, switch to online mode in S7T Config by selecting the
Project > Connect to selected target devices menu command.
15
Select "Technology > S120_CU320_2_DP" in the project tree and select Target device > Load CPU / drive unit to
PG from the shortcut menu. Confirm the confirmation prompt with "Yes".
16
Save the project in S7T Config.
17
Switch to offline mode by selecting the Project > Disconnect from target system menu command.
CPU 317TF-3PN/DP: Controlling a SINAMICS S120 with Safety Functions
Getting Started, 10/2013, A5E02982990-04
4.12 Configuring safety functions on the drive
Configuration
71