Relay output specifications (C24)
Item
Output type
Rated control capacity
Output points per common
Response time
Mechanical lifetime
Electrical lifetime
Surge absorber
Operating mode indicator
Note1) Resistance load
Limitations on number of simultaneous output on points
Keep the number of output points per common which are simultaneously on within the following range as
determined by the ambient temperature.
Circuit diagram
2-10
1a output
2A 250V AC, 2A 30V DC (4.5A per common or less)
8 points/common
off→on
Approx. 10ms
on→off
Approx. 8ms
Min. 20,000,000 operations
Min. 100,000 operations
None
LED display
Description
Note1)