7.4.2 1:1 Communication (Computer link)

System register settings
Settings for COM1 port (AFPG801, AFPG802)
No.
No. 410
COM1 port unit number
Note)
No. 412
COM1 port selection of communication mode
No. 413
Communication format for COM1 port
Note)
No. 415
Baud rate setting for COM1 port
Settings for COM2 port (AFPG802, AFPG806)
No.
No. 411
COM2 port unit number
Note)
No. 412
COM2 port selection of communication mode
No. 414
Communication format for COM2 port
Note)
No. 415
Baud rate setting for COM2 port
The communication format and baud rate (communication speed) should be set to match the connected
computer.
Note) They are set in different bit positions of the same system register no., so the different settings are
possible for port 1 and port 2.
Programming
• For a computer link, a program should be created that allows command messages to be sent and
response messages to be received on the computer side. The PLC automatically sends back a
response to a command. No communication program is required on the PLC side.
• Also, if a software program such as PCWAY is used on the computer side, PLC data can easily be
read and written without having to think about the MEWTOCOL-COM protocol
7-26
Name
Name
Set Value
1
Computer link
Data length: ......
7 bits/8 bits
Parity check: .....
None/Odd/Even
Stop bit: ............
1 bit/2 bit
Terminator: ........
CR
Header: ............
STX not exist
2400 to 115200 bps
Set Value
1
Computer link
Data length: ......
7 bits/8 bits
Parity check: .....
None/Odd/Even
Stop bit: ............
1 bit/2 bit
CR
Terminator: ........
Header: ............
STX not exist
2400 to 115200 bps