Communication Specifications
Computer link
1:1
communi-
cation
Interface
RS232C
AFPG-801
Target
AFPG-802
items
AFPG-806
Half-
Commu-
duplex
nication
communi-
method
cation
Note1) Although it has adequate tolerance to noise, it is recommendable to make the user program to
execute retransmission (in order to improve reliability of the communication when a
communication error occurs due to excessive noises or when a receiver equipment cannot
receive data temporarily).
Note2) The number of units of the PC(PLC) link with RS232C is two.
Communication specifications
Item
Interface
Communication mode
Communication method
Synchronous method
Transmission line
Transmission distance
Note3) Note8)
Baud rate
(to be set by system register)
Computer link
Trans-
General-purpose
mission
serial ommunication
code
MODBUS RTU
Data length
Communication
format
Parity
(to be set by
Stop bit
system register)
Start code
Note4)
End code
No. of connected units
Note1) When connecting a commercially available device that has an RS485 interface, please confirm
operation using the actual device. In some cases, the number of units, transmission distance,
and baud rate vary depending on the connected device.
10-10
General-purpose serial
Note1) 9)
communication
1:N
1:1
communi-
communi-
cation
cation
RS485
RS232C
AFPG-801
AFPG-803
AFPG-802
AFPG-806
AFPG-806
Two-wire,
Half-duplex
half-duplex
communi-
communi-
cation
cation
Specifications
RS232C (non-isolated)
1:1 communicaion
Half-duplex communication
Start stop synchronous system
Multicore shielded line
15 m
2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
ASCII, JIS7, JIS8
ASCII, JIS7, JIS8, Binary
Binary
7 bits/8 bits
None/Even/Odd
1 bit/2 bits
STX/No STX
CR/CR+LF/None/ETX
Note5) 6) 7)
2 units
Note1) 9)
PC(PLC)
1:N
link
communi-
cation
RS232C
RS485
RS485
AFPG-801
AFPG-803
AFPG-802
AFPG-806
AFPG-803
AFPG-806
Two-wire,
Token bus
half-duplex
(Floating
communi-
master)
cation
RS485 (isolated)
1:N communication
Two-wire half-duplex communication
Shielded twisted-pair cable or VCTF
Max. 1200 m
Max. 99 units (Max. 32 units when C-
NET adapter is connected.)
Note1)
MODBUS RTU
1:1
1:N
communi-
communi-
cation
cation
RS232C
RS485
AFPG-801
AFPG-803
AFPG-802
AFPG-806
AFPG-806
Two-wire,
Half-duplex
half-duplex
communi-
communi-
cation
cation
Note1) 2)
Note1) 2)