Cases where rewriting is not possible during RUN
1. When the result of rewriting is a syntax error.
<Example>
When executing the rewriting which does not form the following pair of instructions.
1. Step ladder instructions (SSTP/STPE)
2. Suroutine instructions (SUB/RET)
3. Interrupt instructions (INT/IRET)
4. JP/LBL
5. LOOP/LBL
6. MC/MCE
Also, rewritng is not possible during RUN in case of other syntax errors.
2. During the forced input/output operation
Interrupt restrictions
When using interrupt, high-speed counter, pulse output or PWM output functions, do not perform a
rewrite during RUN.
If a rewrite during RUN is executed, the operation as below will be performed. Exercise caution.
1. Interrupt programs will be disabled. Enable by executing an ICTL instruction once again.
<Example> Using R9034 (rewrite during RUN completed flag)
2. The high-speed counter will continue to count.
Target value match on/off instructions (F166/F167) will continue.
Coincidence interrupt programs will be disabled when the F166/F167 instruction is running.
3. Pulse output and PWM output will be stopped.
State
Instruction number
Continue
F171 (SPDH)
Stop
F172 (PLSH)
Stop
F173 (PWMH)
Continue
F174 (SP0H)
Continue
F175 (SPSH)
Stop
F176 (SPCH)
9-16
Pulse output (with channel specification) (Home position return)
Pulse output (with channel specification) (JOG operation)
PWM output (with channel specification)
Pulse output (with channel specification) (Selectable data table
control operation)
Pulse output (Linear interpolation)
Pulse output (Circular interpolation)