Bit
Meaning
10
Master control by PLC
Note:
This bit should not be set to "1" until the PROFIdrive has returned an appropriate status via ZSW1.9 = "1".
11
Start referencing
12
Reserved
13
External block change
14
Reserved
15
Reserved
STW2 (control word 2)
See function diagram [2444]
Table 10- 7
Description of STW2 (control word 2)
Bit
Meaning
0
Drive data set selection DDS bit 0
1
Drive data set selection DDS bit 1
2
Drive data set selection DDS bit 2
3
Drive data set selection DDS bit 3
4
Drive data set selection DDS bit 4
5...6
Reserved
7
Parking axis
8
Travel to fixed stop
(not with telegrams 9, 110)
9
Reserved
10
Reserved
11
Motor changeover
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Communication PROFIBUS DP/PROFINET IO
10.1 Communication according to PROFIdrive
Remarks
1
Control by PLC
This signal must be set so that the process data
transferred via PROFIdrive are accepted and
become effective.
0
No control by PLC
Process data transferred via PROFIdrive are
rejected - i.e. assumed to be zero.
1
Start referencing
0
Stop referencing
-
-
0/1
External set change is initiated
0
No effect
-
-
-
-
Remarks
-
Drive data set selection
(5 bit counter)
-
-
-
-
-
-
1
Request parking axis (handshake with ZSW2 bit
7)
0
No request
1
Select "Travel to fixed stop"
The signal must be set before the fixed stop is
reached.
1/0
Deselect "Travel to fixed stop"
The signal must be set before the fixed stop is
reached
-
-
-
-
0/1
Motor changeover complete
0
No effect
BICO
BI: p0854
BI: p2595
-
BI: p2633
-
-
BICO
BI: p0820[0]
BI: p0821[0]
BI: p0822[0]
BI: p0823[0]
BI: p0824[0]
-
BI: p0897
BI: p1545
-
-
BI: p0828[0]