● Activation via PROFIsafe or TM54F
● SINAMICS S120: As of firmware version 2.5 SP1
● SIMOTION D 410 SP2 (available soon)
● SIMOTION D4x5:
● Safe actual value acquisition (see chapter "Safe actual value acquisition")
● An activated speed controller in the drive
● Overview of hardware components that support the Extended Functions:
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
– A13000 --> License not sufficient
– LED READY --> Flashes greed/red at 0.5 Hz
NOTICE
Per single Control Unit, either control via PROFIsafe or TM54F is permitted. Mixed
operation is not permitted.
– when controlled by TM54F:
As of firmware version 4.1 SP1 (as of SINAMICS S120 integrated with firmware
version 2.5 SP1)
– when controlled by PROFIsafe:
As of firmware version 4.1 SP1 HF6 (as of SINAMICS S120 integrated with firmware
version 2.5 SP1 HF5)
– Control Unit CU310 with order no.: 6SL3040-0LA00-0AA1/6SL3040-0LA01-0AA1
– Control Unit CU320 with order no.: 6SL3040-...-0AA1 and version C
– D410 DP with order no.: 6AU1 410-0AA00-0AA0 release C
D410 PN with order no.: 6AU1 410-0AB00-0AA0 release C
– D425 with order no.: 6AU1 425-0AA00-0AA0 HW release D
D435 with order no.: 6AU1 435-0AA00-0AA1 HW release D
D445 with order no.: 6AU1 445-0AA00-0AA0 HW release B
– CX32 (without restrictions)
– Motor Modules booksize with order no.: ...3 or higher
– Motor Modules booksize compact
– Power Modules blocksize
– Control Unit adapter CUA31 with order no.: 6SL3040-0PA00-0AA1
– Control Unit adapter CUA32 with order no.: 6SL3040-0PA01-0AA0
– Sensor Module SMC20, SME20/25/120/125
– Motors with DRIVE-CLiQ interface (not with resolver encoder)
Safety Integrated basic functions