Chapter 4 Display and Operation
Figure 4.4

4.4.3 Force Output Control Operation

For testing, the digital outputs can be forced to be activated (ON) or inactivated (OFF)
by using parameter P2-08 and P4-06. First, set P2-08 to 406 to enable the force output
control function and then using P4-06 to force the digital outputs to be activated.
Follow the setting method in Figure 4.5 to enter into Force Output Control operation
mode. When P4-06 is set to 2, the digital output, DO2 is activated. When P4-06 is set
to 7, the digital outputs, DO1, DO2 and DO3 are both activated. The parameter setting
value of P4-06 is not retained when power is off. After re-power the servo drive, all
digital outputs will return to the normal status. If P2-08 is set to 400, it also can switch
the Force Output Control operation mode to normal Digital Output (DO) Control
operation mode.
The DO function and status is determined by P2-18 to P2-22. This function is enabled
only when Servo Off (the servo drive is disabled).
4-10
info@varitel.com - www.varitel.com - Tel. (54) 11-4243-1171 / Fax: (54) 11-4292-7545
Manuel Baliña 456, Lomas de Zamora (B1832CCJ) Buenos Aires, Argentina.
VARITEL INGENIERIA ELECTRONICA S.A.
ASDA-B2
Revision September 2013