5.3 JOG Trial Run without Load

It is very convenient to use JOG trial run without load to test the servo drive and motor as it
can save the wiring. The external wiring is not necessary and the users only need to
connect the digital keypad to the servo drive. For safety, it is recommended to set JOG
speed at low speed. Please refer to the following steps to perform JOG trial run without
load.
STEP 1: Turn the drive ON through software. Ensure that the setting value of parameter
P2-30 should be set to 1 (Servo On).
STEP 2: Set parameter P4-05 as JOG speed (unit: r/min). After the desired JOG speed is
set, and then press SET key, the drive will enter into JOG operation mode
automatically
STEP 3: The users can press UP and DOWN key to change JOG speed and press
SHIFT key to adjust the digit number of the displayed value.
STEP 4: Pressing SET key can determine the speed of JOG operation.
STEP 5: Pressing UP key and the servo motor will run in CCW direction. After releasing
UP key, the motor will stop running.
STEP 6: Pressing DOWN key and the servo motor will run in CW direction. After
releasing DOWN key, the motor will stop running.
N (CW) and P(CCW) Definition:
CCW (Counterclockwise): when facing the servo motor shaft, CCW is reverse
running.
CW (Clockwise): when facing the servo motor shaft, CW is forward running.
STEP 7: When pressing MODE key, it can exit JOG operation mode.
Revision September 2013
info@varitel.com - www.varitel.com - Tel. (54) 11-4243-1171 / Fax: (54) 11-4292-7545
Manuel Baliña 456, Lomas de Zamora (B1832CCJ) Buenos Aires, Argentina.
VARITEL INGENIERIA ELECTRONICA S.A.
Chapter 5 Trial Run and Tuning Procedure
5-7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents