Chapter 5 Trial Run and Tuning Procedure

5.5.3 Auto Mode Tuning Flowchart

Set P2-32 to 1 (1: Auto Mode [Continuous adjustment] )
The servo drive will continuously estimate the system inertia, save the measured load
inertia value automatically and memorized in P1-37 every 30 minutes by referring to
the frequency response settings of P2-31.
P2-31 : Auto Mode Stiffness Setting (Default setting: 80)
In Auto mode and Semi-Auto mode, the speed loop frequency response settings are
as follows:
1 ~ 50Hz : Low stiffness and low frequency response
51 ~ 250Hz : Medium stiffness and medium frequency response
251 ~ 550Hz : High stiffness and high frequency response
Adjust P2-31: Increase the setting value of P2-31 to enhance the stiffness or reduce
the noise. Continuously perform the adjustment until the satisfactory performance is
achieved.