Overall Reset Using The Mode Selector (On Screen) - Siemens SIMOTION P320-4 E Commissioning And Hardware Installation Manual

Hide thumbs Also See for SIMOTION P320-4 E:
Table of Contents

Advertisement

Commissioning (software)
9.9 SIMOTION P overall reset
● Data saved with the _savePersistentMemoryData(), _saveUnitDataSet(),
_exportUnitDataSet(), and RAMtoROM commands.
If the retain data is backed up (with _savePersistentMemoryData()), this data is backed up
again to the non-volatile data after the overall reset. Thus, the user can perform an overall
reset to force the saved retain data to be restored.
● Licenses
The technology packages and user data (configuration data, programs, parameter
assignments) you previously backed up to an external CFast card by means of the Copy RAM
to ROM command are transferred to the non-volatile data area of the SIMOTION P320-4 after
the overall reset.
Thus, an existing configuration on the external CFast card is loaded to the SIMOTION device
following the overall reset.
Further information
Data storage concept overview (Page 97)
9.9.2

Overall reset using the mode selector (on screen)

For SIMOTION P320-4, the overall reset using a simulated mode selector is performed using
the SIMOTION P State application.
Proceed as follows to initiate an overall reset:
1. Turn the mode selector switch of the SIMOTION application SIMOTION P State to STOP
by clicking on STOP.
Figure 9-17
2. Turn the mode selector switch to MRES and hold this position until the STOP LED stops
flashing.
If you now release the MRES position, the switch automatically returns to the STOP position.
3. You must turn the switch back to the MRES position within three seconds. The overall reset
will now be performed.
The SIMOTION P320‑4 has completed the overall reset when the STOP LED lights up.