D8128D address settings

The D8128D OctoPOPIT has two sets of DIP switches. Use the DIP switches on the top of the
unit (with the terminal strip along the left edge) to set the address for the OctoPOPIT. Use the
DIP switches at the bottom of the unit to enable or disable individual points connected to the
OctoPOPIT. The D82128D connects to the control panel through a B600.
ZONEX 1
Output
number
9 to 16
17 to 24
25 to 32
33 to 40
41 to 48
49 to 56
57 to 64
65 to 72
73 to 80
81 to 88
89 to 96
97 to 104
105 to 112
113 to 120
121 to 127
Notice!
For the D8128D OctoPOPITs assigned to Points 121 to 127, 241, and 247, set Point Input
Switch 8 to the OPEN position.
The B9512G uses Points 9 to 127 on ZONEX 1 and Points 129 to 247 on ZONEX 2.
B8512G uses only Points 9 to 99 on ZONEX 1.
Bosch Security Systems, Inc.
B9512G output numbers
521 – 528
531 – 538
541 – 548
551 – 558
561 – 568
571 – 578
581 – 588
591 – 598
D8128D address switches
1
2
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
Installation Manual
B8512G output numbers
3
4
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
Appendix | en 167
ZONEX 2
5
Output
number
--
129 to 136
--
137 to 144
--
145 to 152
--
153 to 160
--
161 to 168
--
169 to 176
--
177 to 184
--
185 to 192
--
193 to 200
--
201 to 208
--
209 to 216
--
217 to 224
--
225 to 232
--
233 to 240
--
241 to 247