Ul 365 - Police Station Connected Burglar Alarm Units And Systems; Ul 636 - Holdup Alarm Units And System; Required Programming To Meet Ul 864 - Bosch B9512G-E Installation Manual

Table of Contents

Advertisement

118 en | Approved applications
Two D126 Batteries = 14 Ah
One D1218 Battery = 17.2 or 18 Ah
Table 19.13: Household fire ampere-hour (Ah) calculation formula
19.5
UL 365 - Police Station Connected Burglar Alarm Units and
Systems
In a mercantile burglar alarm system, a mercantile alarm sounding device located within a
building but outside the protected area is acceptable provided it is rated for outside service
and alarm conditions are transmitted to:
or
In a mercantile burglar alarm system, an alarm sounding device located within the area of
greatest protection, or outside the area of greatest protection but within an area protected by
an alarm system, and that shares a common control unit with the system installed in the area
of greatest protection, is acceptable provided it is rated for inside service and alarm
conditions are transmitted to:
or
Mount an inside sounding device at least 10 feet (3.05 m) above the floor or at the surface of
the ceiling. When fixed construction within the area could provide access for an intruder, the
mount the alarm sounding device at least 4 ft (1.2 m) as measured horizontally, away from the
edges of the fixed construction or at least 10 ft (3.05 m) above it so as to minimize access by
an intruder.
19.6

UL 636 - Holdup Alarm Units and System

When using the system for hold-up operation, a hold-up point should be assigned to a point as
follows:
When using Modem Format communication type, the unique point text should be set to ''Hold-
Up'', or equivalent language per the AHJ.
When using Contact ID communication type, because the Contact ID system doesn't provide
custom text, the hold-up point should be associated as a "hold-up" point at the receiving
station. Set Area # Delay Restorals as follows:
19.7

Required programming to meet UL 864

This section identifies the programming requirements you must make in order to comply with
UL 864 Commercial Fire applications.
2018.07 | 10 | F.01U.303.996
The dispatch location of the law enforcement agency having jurisdiction over the
protected property
A central station or residential monitoring station complying with the Standard for
Central-Station Alarm Services, UL 827.
The dispatch location of the law enforcement agency having jurisdiction over the
protected property
A central station or residential monitoring station complying with the Standard for
Central-Station Alarm Services, UL 827.
P## Point Type set to 24-hr, P## Point Response set to 0 (Point is constantly armed
regardless of the status of the system.)
P## Invisible Point set to Yes (Keypads do not display alarm activity from this point.)
Area # Delay Restorals = No (Restoral report is sent when point restores.)
Installation Manual
Control Panels
Bosch Security Systems, Inc.