Address Settings; Supervision; Sdi Address 88; D9133Dc Direct Connect Programming Module - Bosch D7212GV2 Operation And Installation Manual

Hide thumbs Also See for D7212GV2:
Table of Contents

Advertisement

.
The DX4010i can be installed up to 305 m (1000 ft.)
from the control panel, using 0.8 mm (22 AWG) wire.
The DX4010i was not investigated by UL. Do not use
DX4010i in UL Listed installations.
The D9133 can be installed up to 305 m (1000 ft.) from
the control panel using 1.2 mm (18 AWG) wire. The
D9133 was not investigated by UL. Do not use D9133
in UL Listed installations.

12.4.2 Address Settings

No jumper settings are required for the D9133 (SDI
Address 80) for home or building automation purposes
(Figure 20). Remove the jumper shunts for this purpose.

Figure 20: D9133 Jumper Settings

1
80
The DX4010i has specific DIP switch settings for SDI
Address 80 when home or building automation is
desired. Figure 21 shows the correct settings for
Address 80.

Figure 21: DX4020i DIP Switch Settings

1
P3
3
2
1 - Address DIP switches
2 - OFF position
3 - ON position
4 - SDI Address 80 switch settings
Bosch Security Systems, Inc. | 5/05 | F01U003805B
D7212GV2 | Operation and Installation Guide | 12.0
2
3
4
LED
ENABLE
Rx Tx
Tx
Rx
BUS
SER
P2
P6
P1
DB9 GND
ENABLE
ON
ON
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
4
8
16
32
64 128
1
2
4
8
16
32
64 128
4

12.4.3 Supervision

Supervision of the serial interface module is available
through programming. Supervision of the serial
interface module is available through programming.
Supervision is not required to use a DX4010i or a
D9133.
If supervised, and the serial interface module does not
respond to control panel supervision polls, the control
panel sends an SDI Failure Report to the receiver. If it
fails to communicate with the DX4010i or the D9133,
SERVC SDI 80 displays at the keypad. The SDI
Failure Report includes the address of the troubled
module indicating which module needs service.
12.5

SDI Address 88

SDI Address 88 is available with the D7212GV2
Control Panel and is used for several different
applications. When using SDI Address 88, connect
only one listed device at a time.
12.5.1 D9133DC Direct Connect Programming
Module
Use the D9133DC Direct Connect Programming
Module to handle local programming of the
D7212GV2 Control Panel. In addition, the D9133DC
allows diagnostic and history retrieval. D9133DC is not
UL Listed.
Connecting the D9133DC
1. Configure D9133DC for SDI Address 88. To
program the control panel when the reset pin is in
the unlocked position, program Enable SDI RPS to
Yes in the GV2AUX handler.
2. Connect D9133DC to Com Port 1 or Com Port 2
on the PC. The D9133DC has a DB-9 female serial
connector. A null-modem cable must be purchased
separately to connect the D9133DC to a PC.
3. Using 0.8 mm (22 AWG) or 1.2 mm (18 AWG)
wire, connect the D9133DC SDI terminals (SDI
PWR, SDI A, SDI B, and SDI COM) to the
control panel's SDI terminals (Terminals 29 to 32).
To send or receive the control panel's program, place
the Reset Pin in the Locked or Unlocked position.
Locking the Reset Pin when programming
the control panel improves the uploading
and downloading times.
Used as an External Modem
The D9133DC can operate as an external modem
when using Remote Programming Software (RPS) with
the control panel. Refer to the D7212GV2 Program Entry
Guide (P/N: F01U003804) for programming details.
SDI Devices
49