Fire Applications - Bosch B9512G-E Installation Manual

Table of Contents

Advertisement

Control Panels
Safe and Vault protective circuits
To test the devices that protect the safe(s) or vault(s) without sounding the bell, specify the
devices' points as controlled zones and supervised for trouble conditions. Refer to Point
Profile in RPS Help, in the Installer Services Portal programming tool (available in Europe,
Middle East, Africa, and China) Help or in the control panel's Program Entry Guide for more
information.
Bell configuration
Bell test
Exit delay
Do not program the control panel's maximum exit delay longer than 30 seconds.
Equipment requirements
19.1.3

Fire applications

You can use UL Listed fire initiating devices not requiring electrical compatibility evaluation in
any application. For example, the four-wire smoke detectors, heat detectors, waterflow
switches, and manual pull stations are suitable fire initiating devices. Consult the individual
component specification and installation documents to determine suitability.
Notice!
UL requires that the control panel supervises any device powered from a power output.
Bosch Security Systems, Inc.
UL 365 requires a bell time of 15 to 30 min. The Rothenbuhler 5110 Bell provides
selectable bell time through manipulation of its jumpers. Refer to the manufacturer's
installation instructions for more information.
In addition to the jumper settings inside the bell, you can activate the control panel for a
bell time of 15 min.
UL 365 requires a Bell Test at arming and you must enable it in control panel
programming.
Refer to the various bell parameters in RPS Help, in the Installer Services Portal
programming tool (available in Europe, Middle East, Africa, and China) Help or in or the
control panel's Program Entry Guide for more bell time and test programming information.
To enable the bell test feature, you enable an unused area of the control panel. Enable
the bell test feature for the unused area only. Program OUTPUT B as the area bell output
for the unused area.
Make all passcodes with authority to arm the safe or vault and also send a Closing Report
valid in this area. Program the area for a five-second exit delay.
To complete the installation for this feature, connect the output to a D134 Dual Relay
Module.
Control panel
Two (2) D126 12 V, 7 Ah batteries
Two (2) D1218 12 V, 18 Ah batteries
B520 Auxiliary Power Supply Module/or D8132 Battery Charger Module
Two (2) D8108A Enclosures
D122 Dual Battery Harness
D122L Dual Battery Harness
D133 Relay Module
EVD System (Listed Safe/Vault)
Installation Manual
Approved applications | en 109
2018.07 | 10 | F.01U.303.996

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B9512gB8512g-eB8512g

Table of Contents