Use the following parameters for commercial fire alarm installations. Check with your local
Authority Having Jurisdiction.
UL 864 programming recommendations
Prompt
Phone Line Fail Report
Phone Line Restoral Report
Fire Walk Start Report
Fire Walk End Report
Cancel Report
KP# Scope
Function Lock (within the
Keypads section
Reset Sensors
Fire Test
Bosch Security Systems, Inc.
Permitted in UL 864?
(Yes/No)
Yes
Yes
Yes
Yes
No
Yes
For IP Communications to a D6600 Receiver
Yes
Yes
Yes
Yes
Yes
Yes
Possible Settings
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Panel Wide, Account Wide, Area
Wide, Custom, No Keypad
Yes / No
Disable/Enable/Passcode Protect
Disable / Enable / Passcode Protect
Installation Manual
Possible settings
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
NEOL / DEOL /
2kEOL
Yes / No
IPV4 address or
hostname
200s, 300s, 1hr
0, 5 to 65535
seconds*
5 to 65535 seconds
1 to 255
Recommendation
Yes
Yes
Yes
Yes
Yes
Do not program No Keypad
No
Enable
Enable
Approved applications | en 121
Settings permitted in
UL 864
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to No
Single / 2kEOL
Set to Yes
Program a valid IPV4
address or hostname
Select the Receiver
Supervision Time required
by your AHJ (200 seconds
or 300 seconds)
Program as necessary
Program as necessary
Program as necessary