Required Values To Achieve 180S (Ulc)/200S (Ul) Supervision Interval; Ulc - Bosch B9512G-E Installation Manual

Table of Contents

Advertisement

122 en | Approved applications
Prompt
L## Reset Sensors
L## Fire Test
U### User Group
P## Ring Until Restored
P## Cross Point
D# Fire Unlock
19.8
Required values to achieve 180s (ULC)/200s (UL) supervision
interval
Applicable for both IP and cellular communication.
Requirement
Supervision interval for IP and Cellular
communication is 200 seconds (UL)
Supervision interval for IP and Cellular
communication is 180 seconds (ULC)
19.9

ULC

Conduct testing monthly, with the primary de-energized.
2018.07 | 10 | F.01U.303.996
Possible Settings
Disable / Enable
Disable / Enable
0 to 32
Yes / No
Yes / No
Yes / No
Parameter
Panel Wide Parameters > Enhanced Communications > Receiver
Supervision Time set to 200 seconds
Panel Wide Parameters > Enhanced Communications > Receiver
Supervision Time set to Custom, Poll Rate set to 89, ACK Wait
Time set to 15, and Retry Count set to 5
Installation Manual
Recommendation
If Reset Sensor is set to Passcode
Protect, set this to Enable
If Fire Test is set to Passcode Protect,
set this to Enable
Program as 0
May be required for Waterflow,
otherwise No
Set to No for Fire devices.
No
Bosch Security Systems, Inc.
Control Panels