Bosch B9512G-E Installation Manual page 119

Table of Contents

Advertisement

Control Panels
Notice!
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply
with the requirements in the Standard for Control Units and Accessories for Fire Alarm
Systems, UL 864, you must limit certain programming features or options to specific values.
UL 864 programming requirements
Product feature/option
Phone 1 through 4
Phone Supervision
Alarm On Fail
Buzz On Fail
Two Phone Lines
Expand Test Report
Fire Reports
R# Fire Supervisory Missing
Test Reports
AC Fail Report
AC Restoral Report
Battery Missing Report
Low Battery Report
Battery Restoral Report
R# Service Start Report
R# Service End Report
R# Fire Walk St Report
R# Fire Walk End Report
R# Walk Test St Report
R# Walk Test End Report
Ground Fault Detection
AC Fail Time
AC Fail Display
AC Tag Along
AC/Battery Buzz
Bosch Security Systems, Inc.
Permitted in UL 864?
(Yes/No)
Yes
Yes
No
Yes
Yes
Yes
Yes
Required
Yes
Yes
Yes
Yes
Yes
Yes
Required
Required
Required
Required
Required
Required
Yes
Yes
Yes
Yes
Yes
Installation Manual
Possible settings
24 characters
0 to 240 seconds
Yes / No
Yes / No
Yes / No
Yes/No
Yes / No
Yes/No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Enabled / Disabled
1:00 to 90:00 min
10 to 300 seconds
Yes / No
Yes / No
Approved applications | en 119
Settings permitted in
UL 864
Program a valid phone
number
10 to 200 seconds
Set to No
Set to Yes
Set to Yes when using PSTN
communications.
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Yes
Set to Enabled
Enter 1:00
10 to 200 seconds
Set to Yes
Set to Yes
2018.07 | 10 | F.01U.303.996