Power Supply Side Wiring - Bosch B9512G-E Installation Manual

Table of Contents

Advertisement

98
en | System wiring diagrams
18.1

Power supply side wiring

BAT 2-
BAT 2+
BAT 1-
BAT 1+
7
6
9
8
AUX PWR
ALARM TRIG
SUPV IN
ALARM CKT
+
12
11
Callout ᅳ Description
1 ᅳ D113 Supervision module, battery lead (if required
by local AHJ)
2 ᅳ Batteries
3 ᅳ D122/D122L Dual Battery Harness, as required
4 ᅳ To supervision point
5 ᅳTransformer
6 ᅳ B520 Auxiliary Power Supply Module
7 ᅳ To powered devices
2018.07 | 10 | F.01U.303.996
CHGR-
VAUX+
SUPV
CHGR+
10
COM
-
5
BATTERY STATUS
Off: Normal
On: Missing
Quick Flash: Low
Slow Flash:
Charging
Low 12.1 VDC
Load Shed 10.2 VDC
Do not connect
to a receptacle
controlled by
a switch.
CLASS 2
1
16.5 VAC 40 VA 60 Hz
2
TRANSFORMER
3
+ AUX POWER
BATTERY (
4
BATTERY ( + )
5
OUTPUT
6
A (1)
OUTPUT
7
B (2)
OUTPUT
8
C (3)
9
COMMON
10
EARTH GROUND
WARNING!
Multi-Battery
installation requires
Model D122 or D122L
Dual Battery Harness.
Improper installation
can be a fire hazard .
13
USB POWER
STATUS
USB
Callout ᅳ Description
8 ᅳ To control panel SDI2 wiring
9 ᅳ D192G Notification appliance module
10 ᅳ To OUTPUT A (1) or OUTPUT B (2)
11 ᅳ 560 Ω, 2 W EOL resistor (P/N: 15-03130-005)
12 ᅳ Listed audible signaling devices rated at 12.0 VDC
nominal (do not use vibrating type horns)
13 ᅳ To earth ground
Installation Manual
All exte
Require
POWER SUPPL
The Power S
-
)
refer to the B
Battery: Replace every 3 to
5 years with one or two
Model D126 or D1218 12V
Lead Acid Batteries.
The system is intended
panel has been approv
RevPol.
WARNING!
To prevent risk of shock,
disconnect AC power and
communication lines before
servicing.
ON-BOARD POINTS
Owner I
be removed by
Voltage Ranges: Open 3.7 - 5.0 VDC,
WARNING!
Incorrect wiring will
1 k
End-of-line-Resistors Required (P/N 15093130-004),
damage this
equipment.
Point 1
Point 2
Point 3
Point 4
Devices powered by
any output must be
supervised.
11
12
13
14
15
16
B
A
L
S
I
E
N
K
T
POINT 1 COM POINT 2 POINT 3 COM POINT 4
ETHERNET
Bosch Security Systems, Inc.
Control Panels
Point 5 Point 6
Point 7 Point 8
17
18
19
20
21
22
POINT 5 COM POINT 6 POINT 7 COM POINT 8

Hide quick links: