6.0 Installation Guide for UL
Listed Systems
6.1

FPD-7024 UL Listings

The FPD-7024 is UL Listed for the following:
Commercial Fire Alarm (Type Service;
Auxiliary, Local, Central Station, and Remote
Station; Type Initiating: Automatic, Manual,
Sprinkler Supervisory, and Waterflow), UL
Standard UL864.
Install the control panel according to NFPA 72 for
Commercial Fire installations.
6.2

Installation Considerations

Failure to install and program the control panel
according to the requirements in this section voids
the listing mark of Underwriters Laboratories, Inc.
The standby battery capacity is
40 Ah @ 24 VDC.
The total nominal existing must not exceed
1.25 A in standby or 4 A when in alarm.
The control panel must be mounted indoors
and within the protected area.
Grounding must be according to article 250 of
the NEC (NFPA 70).
Points must be connected to UL Listed,
compatible devices.
The ground wire provided with the enclosure
must be connected between the door and the
enclosure using the supplied nuts.
Do not program the ground start feature.
Select Phone Monitoring if the digital alarm
communicator transmitter (DACT) feature is
used.
6.3

Programming the FPD-7024

The system must be tested after
installation and after any re-programming,
including programming performed by
downloading.
When used in UL Listed installations, the control
panel must conform to certain programming
requirements. Section 6.3.1 and 6.3.2 contain a list
of the required program entries and required
accessories for specific UL Listed installations.
Bosch Security Systems, Inc. | 1/10 | F01U008458-03

Installation Guide for UL Listed Systems

6.3.1
Commercial Fire Alarm (Central Station
[DACT] and Local)
Required Accessories
At least one Bosch Security Systems, Inc. Model
D285 Smoke Detector with a D287, D288, D292, or
D293 Series Base; or another UL Listed compatible
smoke detector.
At least one D432A Horn Strobe or D443 Bell
(provides 85 dB for UL985 and NFPA 72
requirements; other UL Listed compatible devices
with a voltage range of 20 to 31 VDC can be used)
is required for this application and must be installed
inside the protected area.
Four-wire detectors must be used with UL Listed
power supervision devices. A compatible UL Listed
four-wire detector is the Bosch Security Systems,
Inc. D285 in a D292 or D293 Series Base. A
compatible Listed relay is the Bosch Security
Systems, Inc. D275.
All points must be used with the resistor provided.
Report Programming
Program non-supervisory and supervisory reports
for those points used.
Program trouble reports.
Set AC Failure Report Delay for 25% of estimated
standby time, or set to send a report at 25%
depletion of battery capacity.
Set automatic test report frequency to occur at
least every 24 hours.
Timer Programming
Program Auto Silence Time for not less than five
minutes, or to "0" to disable auto-silence operation.
Point Programming
For fire points: open = trouble, latching.
Alarm Output Programming
Program notification appliance circuits to activate
from the appropriate input points.
Communications Programming (if Used for
Central Station Service)
Select a communication format compatible with the
central station.
Enable monitoring of both phone lines.
6.3.2

UL Listed Accessory Devices

D132B Multi-use Reversing Relay Module
The D132B is a multi-purpose, fully configurable,
smoke power-reversing module for activating
detectors with local annunciation. The D132B
operates both two-wire and four-wire circuits and