Power Loss Of Fpa-5000 Components - Bosch FPA-5000 System Information Manual

Modular fire panel
Hide thumbs Also See for FPA-5000:
Table of Contents

Advertisement

Modular Fire Panel
Number of functional modules
ANI 0016 A
BCM-0000-B
CZM 0004 A
ENO 0000 B
FPE-5000-UGM
IOP 0008 A
IOS 0020 A
IOS 0232 A
LSN 0300 A
LSN 1500 A
NZM 0002 A
RMH 0002 A
RML 0008 A
7.2

Power loss of FPA-5000 Components

Component
ANI 0016 A
BCM‑0000‑B
CZM 0004 A
ENO 0000 B
FMR-5000-C
FPE-5000-UGM
IOP 0008 A
IOS 0020 A
IOS 0232 A
LSN 0300 A
LSN 1500 A
MPC-xxxx-C
NZM 0002 A
PRD 0004 A
Bosch Sicherheitssysteme GmbH
Power loss
0.62 W (all LEDs lit)
0.96 W (controller + green LED lit)
1.44 W (per AUX with 1.06 A load)
1.65 W (for a line with 100 mA load)
3.36 W (for 4 lines with 100 mA load each)
1.44 W (1 relay activated)
7.80 W (4 relays activated + key deposit heating
active)
5.52 W
0.17 W
0.24 W
0.36 W
0.36 W
1.50 W (AUX with 490 mA load)
2.72 W (LSN)
8.00 W (AUX)
14.70 W (LSN with 750 mA load)
5.40 W
0.96 W
0.07 W
System Information
Technical Data | en 145
Max. number
32
8
32
8
4
32
4
4
32
11
8
32
32
09.2017 | 11.3 | F.01U.028.089