154 en | Technical Data
Cable length
Number of LSN elements
LSN line current
Auxiliary supply AUX
(28 V DC)
Space required (H x W x D)
Weight
Installation of the power supply unit is described in LSN 0300 A LSN improved Module 300 mA,
page 113.
7.5.10
LSN 1500 A LSN improved Module 1500 mA
Operating and display elements
Input voltage
Output voltage
Maximum current consumption
Nominal current consumption
Cable length
Number of LSN elements
LSN line current
Auxiliary supply AUX
(28 V DC)
Space required (H x W x D)
Weight
09.2017 | 11.3 | F.01U.028.089
LSN
Auxiliary supply AUX
Module
LSN
AUX
Standby
Alarm
max. 1600 m, depending on configuration and cable
type
max. 127 LSN classic elements
max. 254 LSN improved elements
max. 300 mA, depending on configuration and cable
type
max. 500 mA for an LSN loop (ERT technology) or 2 x
max. 500 mA with 2 stubs
approx. 127 x 96 x 60 mm
approx. 225 g
2 LEDs (1 x red, alarm/1 x yellow, fault)
1 button (LED test)
20 V DC to 30 V DC/5 V DC ± 5 %
30 ± 0.85 V DC
28 ± 1.0 V DC
4010 mA at 24 V DC
260 mA at 24 V DC
1.7 x current consumption of the LSN elements
1.2 x auxiliary supply AUX
max. 3000 m, depending on configuration and cable type
Max. 127 LSN classic elements
Max. 254 LSN improved elements
max. 750 mA, depending on configuration and cable type
max. 1500 mA, depending on configuration and cable
type
max. 300 mA when connecting LSN classic elements
max. 500 mA for an LSN loop (ERT technology) or 2 x
max. 500 mA with 2 stubs
approx. 127 x 190 x 60 mm
approx. 440 g