Power Supply; Primary Power Terminals 1 And 2; Primary (Ac) Power Circuit; Installing The Transformer - Bosch D7212GV3 Operation And Installation Manual

Hide thumbs Also See for D7212GV3:
Table of Contents

Advertisement

D7212GV3 | Operation and Installation Guide | 5.0

5.0 Power Supply

5.1

Primary Power Terminals 1 and 2

5.1.1

Primary (AC) Power Circuit

The primary source is a 16.5 VAC, 40 VA, internally-
fused transformer (Bosch Security Systems, Inc.
Model D1640). The control panel draws 200 mA when
idle and 500 mA when in an alarm state. The total
available auxiliary current is 1.4 A.
Transient suppressors and spark gaps protect the
circuit from power surges. This protection relies on
the ground connection at Terminal 10. Ensure that
you connect Terminal 10 to a proper ground. Refer to
Section 4.5 Connecting Earth Ground on page 15.
AC Power Fail
The system indicates an AC power failure when
Terminals 1 and 2 do not have power. The AC Fail
Time parameter sets the number of minutes or
seconds without AC power before the control panel
acknowledges the failure and the number of minutes
or seconds after the power returns before the control
panel acknowledges restored power. Refer to the
D7212GV3 Program Entry Guide (P/N: F01U170808)
for additional information about AC Fail Time.
5.1.2

Installing the Transformer

Do not short-circuit the terminals of the
transformer: Shorting the terminals opens
the internal fuse, causing permanent failure.
Connect the transformer to Terminals 1 and
2 of the control panel before plugging it into
the power source.
1. Use 1.22 mm (18 AWG) wire (minimum) to
connect the transformer to the control panel.
The wire length should be as short as possible.
The maximum length is 15 m (50 ft). Connect the
battery and plug in the transformer.
2. Route telephone and sensor loop wiring away
from any AC conductors, including the
transformer wire.
AC wiring can induce noise and low level voltage
into adjacent wiring. Route data wiring away from
AC and telephone wiring.
Always connect the battery first and then
plug in the transformer.
3. Connect the battery. Refer to Section 5.2.2
Installing the Battery on page 21.
4. Plug the transformer into an unswitched, 120
VAC, 60 Hz power outlet only.
20
Power Supply
5. Secure the transformer to the outlet with the
screw provided.
D8004 Transformer Enclosure Required for Fire
Systems: Use the D8004 Transformer Enclosure for
the D1640 Transformer in fire and combined
fire/burglary applications.
Check with the Authority Having
Jurisdiction (AHJ) about mounting
transformers on specific circuits.
5.2

Secondary Power Terminals

5.2.1

Secondary (DC) Power

A 12 V, 7 Ah (up to 14 Ah) sealed lead-acid
rechargeable battery supplies secondary power for
auxiliary and alarm outputs, and powers the system
during interruptions in primary (AC) power.
Warning - Use Lead Acid Batteries Only:
The charging circuit is calibrated for lead-
acid batteries. Do not use gel-cell or nicad
batteries.
Extra Batteries Increase Back-up Time
To increase battery back-up time, connect a second
12 V battery of equal capacity in parallel to the first
battery. Use a D122 Dual Battery Harness to ensure
proper and safe connection. Refer to the Standby
Battery and Curent Rating Chart in the D7212GV3
Approved Applications Compliance Guide
(P/N: F01U143080).
D1218 Battery
The D1218 is a 12 V, 17.2 or 18 Ah battery for use in
applications requiring extended battery standby time.
Up to two D1218 batteries can be connected when
used with a D122 Dual Battery Harness.
Caution: When connecting two D1218
Batteries to the control panel, both must have
the same capacity (use two 17.2 Ah batteries
or two 18 Ah batteries).
When using two D1218 batteries, use a
separate enclosure, a D122L Dual Battery
Harness, and long leads.