Testing The Power Supply; Testing The Conventional And Lsn Functions; Testing The Addressing/Activation - Bosch FPA-5000 System Information Manual

Modular fire panel
Hide thumbs Also See for FPA-5000:
Table of Contents

Advertisement

142 en | Commissioning
2.
3.
Now perform the function tests (as described in Testing the Power Supply, page 142 to Testing
the Addressing/Activation, page 142).
5.4.2

Testing the Power Supply

1.
2.
3.
4.
5.
5.4.3

Testing the Conventional and LSN Functions

1.
2.
5.4.4

Testing the Addressing/Activation

1.
2.
3.
4.
09.2017 | 11.3 | F.01U.028.089
Connect the laptop on which the FSP-5000-RPS programming software is installed to the
fire detection system.
Load the configuration.
Measure the voltage of the batteries.
The target values are12.0 V to 14.1 V, or 24 V to 28.2 V.
Test the power failure function
Remove the fuse and make sure that the failure of the power supply is indicated on the
display.
Make sure that the time limit for failure of the power supply is set to around 25 min (in
the configuration).
Restore the power supply.
Once the fire detection system is reconnected to the power supply, it automatically goes
into standby mode, and the power supply failure display disappears.
Test the battery failure function:
Remove the cables between the batteries and the BCM module.
Make sure that the time limit for failure of the batteries is set to around 25 min (in the
configuration).
Indication of battery failure can be delayed by up to 15 min.
Reconnect the cables between the batteries and the BCM module.
Once the connection with the batteries has been restored, the battery failure display
must be reset manually.
Testing a conventional/LSN loop:
Disconnect the conventional/LSN loop by detaching the cable connection to the
corresponding functional module.
Failure of the conventional/LSN loop must be indicated on the display.
Restore the connection between the conventional/LSN loop and the corresponding
functional module and reset the error message. Now test all automatic and manual
detectors.
Testing a conventional/LSN stub:
Disconnect the conventional/LSN stub by detaching the cable connection to the
corresponding functional module.
Failure of the conventional/LSN stub must be indicated on the display.
Restore the connection between the conventional/LSN stub and the corresponding
functional module and reset the error message. Now test all automatic and manual
detectors.
Test the activation of the transmission devices (TD/DACT/TSN/GSM/X25/X31) by
triggering the corresponding assigned detector.
Test the activation of the transmission devices (TD/DACT/TSN/GSM/X25/X31) by
initiating the corresponding fault.
Test the activation of extinguishing systems, door controls etc.
Test all internal alarm signaling equipment (e.g. audible and visual notification
appliances).