Modular Fire Panel
–
Maximum load of fault outputs BAT
FAULT, AC FAULT and collective fault
Maximum battery resistance (fault
threshold)
Voltage outputs
–
Display and operating elements
–
–
–
Space required (H x W x D)
Weight
Permissible operating temperature
Permissible storage temperature
Installation of the power supply unit is described in BCM‑0000‑B Battery Controller Module,
page 101.
7.5.3
CZM 0004 A 4 Zone Conventional Module
Input voltage
Maximum current consumption
–
–
Outputs (OUT 1-OUT 4)
–
–
–
Auxiliary power supply (AUX1-AUX4)
–
Space required (H x W x D)
Weight without packaging
Operating and display elements
Bosch Sicherheitssysteme GmbH
for switch outputs
2 switchable outputs
1 green LED
3 yellow LEDs
1 button
Standby mode (all 4 zones)
In case of alarm (all 4 zones)
Maximum output voltage
Maximum output current
Max. line resistance
Max. output current (total of all 4
outputs)
Max. 5.6 A (2 x 2.8 A cannot be connected in
parallel)
0 V/0 - 20 mA
430 mΩ
+24 V (20.4 - 30 V), 2.8 A, battery buffered
(programmable)
Mains power on
Mains fault /fault in battery 1/fault in battery 2
LED test, start charging manually, reset switch
outputs
approx. 127 x 96 x 60 mm
193 g
-5 °C to 50 °C
-25 °C to 85 °C
20 V DC to 30 V DC
5 V DC ± 5%
65 mA (at 24 V DC)
65 mA + 100 mA per zone (at 24 V DC)
20 V DC ± 5%
100 mA ± 10% per zone
2 x 25 Ω per zone
230 mA
approx. 127 x 96 x 60 mm
Approx. 135 g
8 LEDs (4 x red, alarm/4 x yellow, fault)
4 keys (LED test)
System Information
Technical Data | en 151
09.2017 | 11.3 | F.01U.028.089