Nzm 0002 A Notification Appliance Zone Module; Rmh 0002 A Relay Module For Mains Voltage - Bosch FPA-5000 System Information Manual

Modular fire panel
Hide thumbs Also See for FPA-5000:
Table of Contents

Advertisement

Modular Fire Panel
Installation of the power supply unit is described in LSN 1500 A LSN improved Module
1500 mA, page 114.
7.5.11
NZM 0002 A Notification Appliance Zone Module
Operating and display elements
Input voltage
Maximum current consumption
Maximum output voltage
Maximum output current
Space required (H x W x D)
Weight
Installation of the power supply unit is described in NZM 0002 A Notification Appliance Zone
Module, page 116.
7.5.12

RMH 0002 A Relay Module for mains voltage

Operating and display elements
Fuses
Input voltage
Feedback current
Feedback voltage
Maximum current consumption
Standby operation
Both relays tripped
Maximum contact load
Maximum line resistance of feedback lines
Space required (H x W x D)
Weight
Installation of the power supply unit is described in RMH 0002 A Relay Module for Mains
Voltage, page 117.
Bosch Sicherheitssysteme GmbH
Standby mode (both zones)
In case of alarms (both zones)
For supply via panel rail
For external power supply
4 LEDs (2 x red, alarm/2 x yellow, fault)
2 buttons (each on/off)
F1 = T 6.3 A, F2 = T 6.3 A
20 V DC to 30 V DC/5 V DC ± 5 %
max. 8.5 mA per feedback output
max. 30 V DC
10 mA
50 mA
5 A at 120 V/230 V AC or 5 A at 30 V DC
(resistive)
2 x 25 Ω
approx. 127 x 96 x 60 mm
Approx. 135 g
4 LEDs (2 x red, alarm/2 x yellow, fault)
2 buttons (LED test)
20 V DC to 30 V DC/5 V DC ± 5 %
40 mA
65 mA + 500 mA per notification appliance
29.5 V DC
500 mA per notification appliance (in case of
alarm)
3 A per notification appliance (in case of
alarm)
approx. 127 x 96 x 60 mm
Approx. 135 g
System Information
Technical Data | en 155
09.2017 | 11.3 | F.01U.028.089

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents